what's the Metal Material for Enclosures in HV/EHV GIS (Gas-insulated switchgear)/AIS?

HV/EHV GIS (Gas-insulated switchgear) Aluminum alloy Casting Enclosures manufacturer in China,aluminum casting flanges supplier for GIS Terminations,AIS/transformer aluminium alloy parts/enclosure/housings/shell/conductor manufacture,

December 30, 2020

Artisan Industry:Power transmission/Substation transformer accessories supplier,metal products,silicone rubber parts Manufacturer

EN 1706 AlSi7Mg0.3 T6/alloy AK7(A/19) 1583-93/ 444.0 /A04440 / EN AC-42000/Al-Si7Mg/ZL101/5A06

aluminium alloy foundry-precision castings-CNC machining-leak testing-painting

Power transmission/Substation transformer metal parts supplier(aluminium alloy Castings,enclosures,flanges,stainless steel parts,Brass/Copper forgings,CNC machining parts,silicone rubber/insulated products/transformer oil&air seals manufacturer

GIS Steel Enclosures:
There are two basic tasks of the enclosure: to keep the gas pressure inside and to be gas tight so that SF6 will not be released to the atmosphere. Both tasks can be well covered by using sheet steel materials. Cast steel has porosities that cannot guarantee such high gas tightness values as required for GIS.
Steel is relative easy to weld and to form. Therefore, the steel enclosures have been welded by steel sheets that have been mechanically formed to cylinders and then were welded.

GIS Aluminum Enclosures:
Used for the conductors as an extruded pipe or in cast technology. For enclosures aluminum is used in cast technology or with welded sheet materials using longitudinal welds or spiral welding processes.
Extruded pipes can be used as conductors in a straight bus bar section. When conductors are used inside disconnecting or ground switches, the required shape and design requires a casting technology.
The disadvantage of cast aluminum in the early years was that the insulation gas was released to the atmosphere due to its porosity.
Today, most enclosures are manufactured in cast aluminum as the top performer for GIS In pic shown Straight conductor graphic that manufacture by aluminium.

Metal used in GIS Enclosures
Enclosures are normally cast or welded aluminum, although steel is also commonly
used. Steel enclosures require painting on the interior and exterior to prevent rusting.
Aluminum enclosures don’t require painting, but may be painted to improve cleaning,
provide a better appearance, or to optimize heat transfer to the ambient atmosphere.
Deciding between aluminum and steel is based on the cost differences between the
two metals and also on the continuous current. With continuous currents exceeding
roughly 2000 amps, steel enclosures will require non-magnetic inserts of stainless
steel. Otherwise the enclosure material should be changed to all stainless steel or
aluminum.

Grounding Individual Enclosures
The individual metal enclosure sections of the GIS modules are electrically connected.
This is accomplished through either of two means:
1.) The flange’s enclosure joint being a good electrical contact in itself.
2.) With external shunts bolted to the flanges or to grounding pads on the enclosure.
Grounding of Single and Three Phase Enclosures
Earlier single-phase GIS enclosures - were single-point grounded to prevent
circulating currents from flowing in the enclosures. Presently, the practice is to use
‘‘multi-point grounding’’ even though this leads to some electrical losses in the
enclosures due to circulating currents.
Three enclosures of a single-phase GIS - should be bonded together at the ends of
the GIS to encourage circulating currents to flow. These circulating enclosure currents
act to cancel the magnetic field that would otherwise exist outside the enclosure due
to the conductor current.
Three-phase GIS enclosures - do not have circulating currents, but do have eddy
currents in the enclosure, and should also be multi-point grounded. With multipoint
grounding and the many resulting parallel paths for the current from an internal fault
to flow to the substation ground grid, it is easy to keep the touch and step voltages for
a GIS to the safe levels prescribed in IEEE 80.

Pressure Vessel Specifications
Specifications for pressurized vessels in GIS enclosures are established within GIS
standards. The actual design, manufacture, and testing procedures follow the
established pressure vessel standard for the country where the equipment is
manufactured.
Due to the modest pressures involved in GIS enclosures, and the classifying of GIS as
electrical equipment, third party inspections and code stamping of the GIS enclosures
are not mandatory requirements.

Protection of Outdoor Enclosures
GIS equipment will not show the effects of aging, whether installed indoors or out. For
outdoor GIS systems, special measures must be taken to ensure adequate protection
from corrosion, effects of low and high ambient temperatures, and solar UV radiation.